HVAC for non-sterile plants: what WHO’s guidelines expect of air handling
Air handling protects products, people and the environment. The main points of WHO’s HVAC guidance for tablets, capsules and liquids plants.

In this article
Heating, ventilation and air-conditioning (HVAC) is one of the most expensive systems in a pharmaceutical plant, and one of the most often cited in inspections. For non-sterile products, such as tablets, capsules, liquids and creams, the World Health Organization’s guidance is in two parts: TRS 1010, Annex 8 (2018), the guidelines, and TRS 1019, Annex 2 (2019), an interpretation with examples.
What HVAC must achieve
- Protect the product from contamination and cross-contamination.
- Protect people from exposure to active substances.
- Protect the environment from dust and exhaust.
Key points of the guidance
- No unfiltered air: unfiltered air must not enter the manufacturing areas; facilities are normally kept at positive pressure to the outside.
- Pressure cascades and airlocks keep dust from moving between rooms, especially where powders are handled.
- Filtration, air changes and airflow are set by risk to reach the cleanliness, temperature and humidity the products need.
- Dust extraction at the source for dispensing, granulation, compression and coating.
- Commissioning, qualification and maintenance: systems are qualified, monitored and maintained, with filters and pressure differentials checked routinely.
Why it matters in Pakistan
Pakistan’s move towards PIC/S GMP (see PIC/S GMP: the phased plan) and new export-oriented plants such as Highnoon’s Project FORCE make HVAC design a first decision, not an afterthought. Karachi’s heat and humidity also make energy use a big cost; see Solar power for pharma plants.
Cleanroom and HVAC suppliers are part of the Pharma Asia exhibition.
Recirculation or full fresh air?
Recirculating part of the air saves energy, because cooled and dehumidified air does not have to be treated again from scratch. But where powders and potent products are handled, recirculated air can carry dust from one room to another. WHO’s guidance allows recirculation where the risk is controlled, for example with suitable filters, and expects full fresh air or other measures where the risk of cross-contamination is high. The decision should be made by risk assessment for each area.
Designing for Karachi’s climate
- Humidity control: many products and processes need low humidity, which in a humid coastal city takes careful dehumidification.
- Heat load: high outdoor temperatures increase cooling demand; good insulation and sealed buildings help.
- Power backup: air handling must keep running, or restart safely, during power cuts, so production areas stay within limits.
Day-to-day monitoring
- Check pressure differentials between rooms every shift, and investigate any reversal.
- Record temperature and humidity in production and storage areas.
- Replace and test filters on a schedule, and keep the records.
- Requalify the system after major changes and at regular intervals.
A well-designed HVAC system is cheaper to run and easier to defend in an inspection than one that was patched together after the plant was built. Plan it with the process engineers and QA from the start. For the energy side, read Solar power for pharma plants.
HVAC and containment
Plants that handle potent products, such as hormones or cytotoxics, need more than standard HVAC. Containment at the source, such as closed transfer systems or isolators, dedicated air handling, safe filter change and treatment of exhaust air protect workers and other products. Decide on containment early, because it shapes the room layout and the air system.
Questions readers ask
Which WHO documents apply?
TRS 1010, Annex 8 (2018), the guidelines, and TRS 1019, Annex 2 (2019), which interprets them with examples.
Do these cover sterile plants?
No. Sterile manufacturing has stricter requirements; see Annex 1, isolators and RABS on Pulse.
What is a pressure cascade?
A set of rooms kept at different air pressures so that air, and dust with it, flows from cleaner to less clean areas.
Sources
- WHO, TRS 1010 Annex 8: Guidelines on heating, ventilation and air-conditioning systems for non-sterile pharmaceutical products (2018)
- WHO, TRS 1019 Annex 2: HVAC for non-sterile pharmaceutical products, part 2: interpretation (2019)
- WHO Prequalification, HVAC recommendations presentation, December 2024